These temperature and fire monitoring instruments use non-contact infrared (IR) measurement to precisely measure the temperature of targets that are difficult to access directly, such as switchgear and distribution panels, enabling early detection of overheating before it leads to an accident. Each module supports a display and RS-485 communication, allowing multiple temperatures to be monitored simultaneously in conjunction with a monitoring system.
TEMP-IR485
TEMP-IR485 adopts a non-contact temperature measurement method, making it ideal for locations where sensors cannot be installed directly on the target, such as switchgear and distribution panels, and wherever an overheat-prevention system or industrial temperature measurement device is required. With a built-in temperature calculation processor, TEMP-IR485 outputs accurate temperature values without requiring any temperature calculation algorithm in the master controller.
Features
- Measures the target temperature and the ambient temperature of the sensor module simultaneously.
- A built-in laser pointer makes it easy to identify the measurement direction.
- A dedicated temperature calculation processor enables high-precision temperature measurement.
- Adjustable emissivity for different target materials ensures accurate temperature readings.
- Uses MODBUS RTU, the well-established industrial protocol.
Specifications
| Power | 5Vdc |
|---|---|
| Current consumption | 21mA (On Laser : 38mA) |
| Communication | MODBUS RTU 485 |
| Temperature measurement range | -20℃ ~ 270℃ |
| Operating temperature | -20℃ ~ 70℃ (Sensor), -10℃ ~ 40℃ (Laser) |
Product Images
Characteristics
| Parameter | Min | Typ. | Max | Unit |
|---|---|---|---|---|
| Temperature measurement range | -20 | - | 270 | ℃ |
| Operating temperature | -20 | - | 70 | ℃ |
| Measurement time | - | 20 | - | msec |
| Resolution | - | 0.1 | - | % |
| Accuracy | - | ±2 | - | ℃ |
| Standard Start-Up Time | - | 1 | - | sec |
Measurement Items
| Item | Unit | Range | Accuracy | Communication |
|---|---|---|---|---|
| Target temperature | ℃ | -20 ~ 270 | ±2 | ○ |
| Sensor ambient temperature | ℃ | -20 ~ 270 | ±2 | ○ |
Communication Line Diagram

TEMP-IR MULTI
TEMP-IR MULTI adopts a non-contact temperature measurement method, making it ideal for locations where sensors cannot be installed directly on the target, such as switchgear and distribution panels, and wherever an overheat-prevention system or industrial temperature measurement device is required. With a built-in array sensor, TEMP-IR MULTI captures target temperatures across 64 pixels simultaneously, and its integrated temperature calculation processor outputs accurate temperature values without requiring any temperature calculation algorithm in the master controller. It can also be linked with a display device to monitor multiple temperatures at once.
Features
- A built-in 16 x 4 array sensor captures target temperatures across 64 pixels simultaneously.
- Capable of generating thermal images.
- Hot spots on the measurement target can be easily located.
- The module accurately measures the surface temperature of any object within 250ms, without contact.
- Measures the target temperature and the ambient temperature of the sensor module simultaneously.
- A built-in laser pointer makes it easy to identify the measurement direction.
- A dedicated temperature calculation processor enables high-precision temperature measurement.
- Adjustable emissivity for different target materials ensures accurate temperature readings.
- Uses MODBUS RTU, the well-established industrial protocol.
Specifications
| Power | 5Vdc |
|---|---|
| Current consumption | 49.20mA (On Laser : 60.20mA) |
| Communication | MODBUS RTU 485 |
| Temperature measurement range | -30℃ ~ 300℃ |
| Operating temperature | -20℃ ~ 70℃ (Sensor), -10℃ ~ 40℃ (Laser) |
Product Images
Characteristics
| Parameter | Min | Typ. | Max | Unit |
|---|---|---|---|---|
| Temperature measurement range | -30 | - | 300 | ℃ |
| Operating temperature | -20 | - | 70 | ℃ |
| Measurement time | - | 250 | - | msec |
| Resolution | - | 0.1 | - | % |
| Accuracy | - | ±2 | - | ℃ |
| Standard Start-Up Time | - | 1 | - | sec |
| Stabilization Time | - | 1 | - | min |
Measurement Items
| Item | Unit | Range | Accuracy | Communication |
|---|---|---|---|---|
| Target temperature | ℃ | -30 ~ 300 | ±2 | ○ |
| Sensor ambient temperature | ℃ | -30 ~ 300 | ±2 | ○ |