KO EN
HOME Products Multi-Channel Energy Meter

PRODUCTS

Products

Explore the WONSEOK Hi-Tech product lineup.

Multi-Channel Energy Meter

A Multi-Channel Energy Meter lineup that measures and monitors multiple loads simultaneously with a single module.
Designed for large- and small-scale power management systems (PMS, BEMS, FEMS) and remote power metering.

SEMS-Master

SEMS-Master front view

Overview

SEMS-Master is the display and configuration unit for the SEMS-6G. While displaying SEMS-6G data, it communicates with upstream SCADA systems, PLCs, and other equipment over multiple TCP/IP and RS-485 (MODBUS RTU) links, and can log data to USB memory.

It also serves as a display and upstream communication converter for up to 24 MPM-330A/AC units, enabling remote monitoring of power data.

Features

Basic Specifications

Power Supply110V ~ 220VAC
Power Consumption5VA
Operating Temp. / Humidity-20 ~ 60°C / 5 ~ 90% (non-condensing)
Dimensions117(W)mm × 117(H)mm × 108(D)mm

Communication Specifications

UpstreamTCP/IP, RS-485
Protocol : MODBUS RTU
DownstreamRS-232C, RS-485
Protocol : MODBUS RTU
Connected devices : SEMS-6G (24ch three-phase / 72ch single-phase), MPM-330 (24 units)
SEMS-Master wiring terminals
Rear terminal layout

SEMS Master Configuration

SEMS Master system configuration diagram
Example system configuration: switchgear panel · per-circuit measurement · central monitoring room

SEMS-6G

SEMS-6G system configuration
Example configuration: Touch Monitor + SEMS-6G + clamp-type CTs (WST series)

Overview

The SEMS series is designed for large- and small-scale power management systems such as PMS (Power Management System), BEMS (Building Energy Management System), FEMS (Factory Energy Management System), and remote power metering systems.

SEMS-6G is designed around the concept of ‘managing as many loads as possible within a minimal footprint’. Starting from a single module handling six three-phase loads (load: 6EA), it scales up to four modules monitoring as many as 24 three-phase loads, and in three-phase applications it can also measure NEUTRAL CURRENT and ZCT.

It enables highly cost-effective remote power metering for retail complexes, officetels, and commercial buildings.

SEMS-6G 1 module
1 module – 6 three-phase circuits
SEMS-6G 2 modules
2 modules – 12 three-phase circuits
SEMS-6G 3 modules
3 modules – 18 three-phase circuits
SEMS-6G 4 modules
4 modules – 24 three-phase circuits

Features

Measured Parameters

ParameterUnitRangeAccuracyRemarks
Line-to-Line VoltageV69 ~ 710Vrms0.3% F.SLine to Line
Phase VoltageV40 ~ 410Vrms0.3% F.SLine to Neutral
CurrentA0.1 ~ 99990.3% F.S
NEUTRAL CurrentA0.03 ~ 99990.5% F.SThree-phase
FrequencyHz47 ~ 630.3% F.S
Power Factor%-1.000 ~ 1.0000.5% F.SEach phase and three-phase
Active PowerkW0.006 ~ 9,999.9990.5% F.SEach phase and three-phase
Reactive PowerKVAR0.000 ~ 9,999.9990.5% F.SEach phase and three-phase
Apparent PowerKVA0.006 ~ 9,999.9990.5% F.SEach phase and three-phase
Active EnergykWh0 ~ 99,999,999.90.5% F.SEach phase and three-phase
Reactive EnergyKVARh0 ~ 99,999,999.90.5% F.SEach phase and three-phase
Apparent EnergyKVAh0 ~ 99,999,999.90.5% F.SEach phase and three-phase
Power THD%0 ~ 1001[%] F.SEach phase
Voltage THD%0 ~ 1001[%] F.SEach phase
Current THD%0 ~ 1001[%] F.SEach phase
Voltage Unbalance%0 ~ 100Each phase and Total
Current Unbalance%0 ~ 100Total
DIBI0 : OFF, 1 : ON
DOBI0 : OFF, 1 : ON
Temperature-20 ~ 110℃· 1.0℃(-40~0℃)
· 0.5~1.5℃(0~80℃)
· 1.5~2.3℃(80~110℃)

Device Ratings

Power Supply100 ~ 240Vac
Frequency50 ~ 60Hz
Power ConsumptionMax. 7W
Voltage InputUp to 700Vrms (LINE TO LINE)
Current InputPri. 30 ~ 500A / Sec. 100mV
Temperature Measurement-20℃ ~ 110℃
DIGITAL INPUTDRY CONTACT input
DIGITAL OUTPUTAC 250V/5A, DC 30V/5A (resistive load)
or PULSE OUTPUT – 500WH PER 1PULSE
Operating Temperature-10 ~ 50℃
Operating Humidity10 ~ 85% (NON CONDENSING)

Communication Specifications

InterfaceDESCRIPTION
RS-232FULL DUPLEX
TXD+, RXD-, GND – 3WIRE
9600 BPS fixed
1.2M
RS-485HALF DUPLEX
MODBUS RTU protocol
DATA+, DATA- – 2WIRE
4800, 9600, 19200, 38400 BPS selectable
TCP/IPMODBUS TCP/IP protocol
10/100M BPS
Uses CROSS CABLE

MPM-38s / 34s

Overview

MPM-38s/34s are devices installed in distribution boards, panelboards, and MCC panels of any scale to efficiently monitor individual loads; a single module measures 8/4 three-phase loads (24/12 single-phase). Measurement data can be checked on site directly on the LCD, and remote monitoring is available via the communication interface.

Features

Measured Parameters

ParameterUnitMeasuring RangeAccuracyLCDCommunication
VoltageV40.0 ~ 9999V(0.5) phase/line-to-line voltage / 1 decimal place
CurrentA0.040 ~ 9999A(0.5) single-phase 1~24ch, three-phase 8ch / 3 decimal places
FrequencyHz46.0 ~ 65.0Hz(0.5) 1 decimal place
Active PowerkW0.100 ~ 9999(1) single-phase 1~24ch, three-phase 8ch / 3 decimal places
Reactive PowerKVAR0.100 ~ 9999(1) single-phase 1~24ch, three-phase 8ch / 3 decimal places×
Power Factor%1.00 ~ -1.00(1) single-phase 1~24ch, three-phase 8ch / 2 decimal places
Active EnergykWh1 ~ 99,999,999(1) single-phase 1~24ch, three-phase 8ch
Reactive EnergyKVARh0.100 ~ 9999(1) single-phase 1~24ch, three-phase 8ch××
Total CurrentA0.100 ~ 99993 decimal places×
Total Active PowerkW0.100 ~ 99993 decimal places×
Total Active EnergykWh1 ~ 9,999,999×

Product Appearance · Drawings

MPM-38s / 34s product appearance
MPM-38s / MPM-34s appearance
MPM-38s / 34s drawing
MPM-38s / 34s dimensional drawing